ABB DriveIT ACH550-01 User Manual page 240

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Code
Description
2607
SW FREQ CTRL
The switching frequency may be reduced if the ACH550 internal
temperature rises above 90 °C. See Figure. This function allows the
highest possible switching frequency to be used based on operating
conditions. Higher switching frequency results in lower acoustic noise.
0 =
– The function is disabled.
OFF
1 =
– The switching frequency is limited according to the figure.
ON
8 kHz
4 kHz
2608
SLIP COMP RATIO
Sets gain for slip compensation (in %).
• A squirrel-cage motor slips under load. Increasing the frequency as
the motor torque increases compensates for the slip.
• Requires parameter 9904
0 = No slip compensation.
1...200 = Increasing slip compensation. 100% means full slip
compensation.
236
Switching frequency limit
90 °C
ACH550 User's Manual
Range
0...200 kHz
ACS5550
Temperature
100 °C
0...200%
MOTOR CTRL MODE
Parameter listing and descriptions
=
.
SCALAR SPEED