ABB DriveIT ACH550-01 User Manual page 294

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Code
Description
5307
EFB CRC ERRORS
Contains a count of the messages with a CRC error received by
the drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels
generate errors.
• CRC calculations for possible errors.
5308
EFB UART ERRORS
Contains a count of the messages with a character error received
by the drive.
5309
EFB STATUS
Contains the status of the EFB protocol.
0 =
IDLE
messages.
1 =
EXEC
2 =
TIME OUT
between the network master and the EFB protocol.
3 =
CONFIG ERROR
4 =
OFF
addressed to this drive.
5 =
ON
adressed to this drive.
6 =
RESET
7 =
LISTEN ONLY
5310
EFB PAR 10
Specifies the parameter mapped to Modbus Register 40005.
5311
EFB PAR 11
Specifies the parameter mapped to Modbus Register 40006.
5312
EFB PAR 12
Specifies the parameter mapped to Modbus Register 40007.
5313
EFB PAR 13
Specifies the parameter mapped to Modbus Register 40008.
5314
EFB PAR 14
Specifies the parameter mapped to Modbus Register 40009.
5315
EFB PAR 15
Specifies the parameter mapped to Modbus Register 40010.
5316
EFB PAR 16
Specifies the parameter mapped to Modbus Register 40011.
5317
EFB PAR 17
Specifies the parameter mapped to Modbus Register 40012.
290
– EFB protocol is configured, but not receiving any
.
– EFB protocol is initializing.
INIT
– A timeout has occurred in the communication
– EFB protocol has a configuration error.
-
– EFB protocol is receiving messages that are NOT
LINE
-
– EFB protocol is receiving messages that are
LINE
– EFB protocol is performing a hardware reset.
– EFB protocol is in listen-only mode.
ACH550 User's Manual
Range
0...65535
0...65535
0...7
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
0...65535
Parameter listing and descriptions

Advertisement

Table of Contents
loading

This manual is also suitable for:

Driveit ach550-uh

Table of Contents