ACH550 User's Manual
Code
Description
1606
LOCAL LOCK
Defines control for the use of the HAND mode. The HAND mode
allows drive control from the control panel.
• When
LOCAL LOCK
HAND mode.
0 =
NOT SEL
and control the drive.
1 =
1 – Defines digital input
DI
lock.
• Activating the digital input locks out local control.
• De-activating the digital input enable the HAND selection.
2...6 =
2...
DI
setting the local lock.
• See
1 above.
DI
7 =
– Sets the lock. The control panel cannot select HAND, and
ON
cannot control the drive.
8 =
– Defines bit 14 of the Command Word 1 as the control for
COMM
setting the local lock.
• The Command Word is supplied through fieldbus communication.
• The Command Word is 0301.
-1 =
1(
DI
INV
setting the local lock.
• De-activating the digital input locks out local control.
• Activating the digital input enable the HAND selection.
-2...-6 =
DI
as the control for setting the local lock.
• See
1(
DI
1607
PARAM. SAVE
Saves all altered parameters to permanent memory.
• Parameters altered through a fieldbus are not automatically saved
to permanent memory. To save, you must use this parameter.
• If 1602
PARAMETER LOCK
the control panel are not saved. To save, you must use this
parameter.
• If 1602
PARAMETER LOCK
control panel are stored immediately to permanent memory.
0 =
– Value changes automatically when all parameters are
DONE
saved.
1 =
– Saves altered parameters to permanent memory.
SAVE
Parameter listing and descriptions
is active, the control panel cannot change to
– Disables the lock. The control panel can select HAND
DI
6 – Defines digital input
DI
) – Defines an inverted digital input
2(
)...
6(
) – Defines an inverted digital input
INV
DI
INV
) above.
INV
= 2 (
= 1 (
Range
0...8, -1...-6
1 as the control for setting the local
2...
6 as the control for
DI
DI
1 as the control for
DI
0=DONE, 1=SAVE
), parameters altered from
NOT SAVED
), parameters altered from the
OPEN
2...
6
DI
DI
209