ABB DriveIT ACH550-01 User Manual page 185

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

ACH550 User's Manual
Group 04: Fault History
This group stores a recent history of the faults reported by the
drive
Code Description
0401
LAST FAULT
0 = Clear the fault history
(on panel = NO RECORD).
n = Fault code of the last recorded fault.
0402
FAULT TIME 1
The day on which the last fault
occurred. Either as:
• A date – if real time clock is operating.
• The number of days after power on – if real time clock is not used, or
was not set.
0403
FAULT TIME 2
The time at which the last fault occurred. Either as:
• Real time, in format hh:mm:ss – if real time clock is operating.
• The time since power on (less the whole days reported in 0402), in
format hh:mm:ss – if real time clock is not used, or was not set.
0404
SPEED AT FLT
The motor speed (rpm) at the time the last fault occurred.
0405
FREQ AT FLT
The frequency (Hz) at the time the last fault occurred.
0406
VOLTAGE AT FLT
The DC bus voltage (V) at the time the last fault occurred.
0407
CURRENT AT FLT
The motor current (A) at the time the last fault occurred.
0408
TORQUE AT FLT
The motor torque (%) at the time the last fault occurred.
0409
STATUS AT FLT
The drive status (hex code word) at the time the last fault occurred.
0410
DI1-3 AT FLT
The status of digital inputs 1...3 at the time the last fault occurred.
0411
DI4-6 AT FLT
The status of digital inputs 4...6 at the time the last fault occurred.
0412
PREVIOUS FAULT 1
Fault code of the second last fault. Read-only.
Parameter listing and descriptions
Range
fault codes (panel
displays as text)
Date dd.mm.yy/
power-on time in
days
Time hh.mm.ss
-
-
-
-
-
-
000...111(binary)
000...111(binary)
as Par.0401
181

Advertisement

Table of Contents
loading

This manual is also suitable for:

Driveit ach550-uh

Table of Contents