Code
Description
11 =
5,6 – Selects one of three Constant Speeds (1...3) using
DI
and
6.
DI
See above (
12 =
1,2,3 – Selects one of seven Constant Speeds (1...7) using
DI
1,
2 and
DI
DI
• Uses three digital inputs, as defined below (0 =
activated):
DI
DI1
0
1
0
1
0
1
0
1
13 =
3,4,5 – Selects one of seven Constant Speeds (1...7) using
DI
3,
4 and
DI
DI
• See above (
14 =
4,5,6 – Selects one of seven Constant Speeds (1...7) using
DI
5,
6 and
DI
DI
• See above (
15...18 =
active. See Group 36, Timer Functions.
19 =
TIMER
Timers 1 and 2. See Parameter 1209.
-1 =
1(
DI
INV
• Inverse operation: Digital input de-activated = Constant Speed 1
activated.
-2...- 6 =
input. See above.
-7 =
1,2(
DI
1 and
DI
• Inverse operation uses two digital inputs, as defined below (0 =
de-activated, 1 =
1
DI
DI
1
0
1
0
-8 =
2,3(
DI
2 and
DI
• See above (
194
1,2) for code.
DI
3.
DI
DI2
DI3
0
0
No constant speed
0
0
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
1
0
Constant speed 3 (1204)
0
1
Constant speed 4 (1205)
0
1
Constant speed 5 (1206)
1
1
Constant speed 6 (1207)
1
1
Constant speed 7 (1208)
5.
DI
1,2,3) for code.
DI
7.
DI
1,2,3) for code.
DI
1...4 – Selects Constant speed 1 when Timer is
TIMER
1 & 2 - Selects a constant depending on the state of
) – Selects Constant Speed 1 with digital input
2(
)...
6(
) – Selects Constant Speed 1 with digital
DI
INV
DI
INV
) – Selects one of three Constant Speeds (1...3) using
INV
2.
DI
activated):
DI
2
Function
1 No constant speed
1 Constant speed 1 (1202)
0 Constant speed 2 (1203)
0 Constant speed 3 (1204)
) – Selects one of three Constant Speeds (1...3) using
INV
2.
DI
1,2(
)) for code.
DI
INV
ACH550 User's Manual
Range
Function
Parameter listing and descriptions
5
DI
de-activated, 1 =
DI
1.
DI
DI