ACH550 User's Manual
Bit
Name
2
OFF3 CONTROL
3
INHIBIT_
OPERATION
4
RAMP_OUT_ZERO
5
RAMP_HOLD
6
RAMP_IN_
ZERO
7
RESET
8..9 Unused
Serial communications
CONTROL WORD
Valu
e
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time
defined by parameter 2208. Enter
OFF3 ACTIVE, proceed to switch-on
INHIBITED.
Warning! Ensure motor and driven
machine can be stopped using this stop
mode.
1
Enter
OPERATION ENABLED
also the Run enable signal must be
active; see parameter 1601
, if parameter 1601 is set to
ENABLE
COMM, this bit also activates the Run
Enable signal.)
0
Inhibit operation. Enter
.
INHIBITED
1
Normal operation.
Enter RAMP FUNCTION
GENERATOR: OUTPUT ENABLED.
0
Force Ramp Function Generator output
to zero.
Drive ramps to stop (current and DC
voltage limits in force).
1
Normal operation.
Enter
RAMP FUNCTION GENERATOR
ACCELERATOR ENABLED
0
Halt ramping (Ramp Function
Generator output held).
1
Normal operation. Enter
0
Force Ramp Function Generator input
to zero.
0=>1
Fault reset if an active fault exists.
Enter
SWITCH
parameter 1604 is set to
0
Continue normal operation.
Comments
(Note that
RUN
OPERATION
.
OPERATING
-
. Effective if
ON INHIBITED
.
COMM
:
149