ABB DriveIT ACH550-01 User Manual page 159

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

ACH550 User's Manual
Reference scaling. The scaling of the fieldbus references REF1
and REF2 is indicated in the table below.
Reference
Range
REF1
-32767...
+32767
REF2
-32767...
+32767
Note:The setting of parameter 1104 REF1 MIN and 1107 REF2
MIN has no effect on the scaling of the references.
The value 20000 in case of REF1 and the value 10000 in case
of REF2 correspond to a reference value of 100% (see section
Reference handling below).
Serial communications
Reference
Scaling
type
Speed or
-20000 = -
frequency
[par. 1105]
0 = 0
+20000 =
[par. 1105]
Speed or
-10000 = -
frequency
[par. 1108]
0 = 0
+10000 =
[par. 1108]
Torque
-10000 = -
[par. 1108]
0 = 0
+10000 =
[par. 1108]
PID
-10000 = -
Reference
[par. 1108]
0 = 0
+10000 =
[par. 1108]
Remarks
Final reference
limited by
1104/1105.
Actual motor
speed limited
by 2001/2002
[speed] or
2007/2008
[frequency].
Final reference
limited by
1107/1108.
Actual motor
speed limited
by 2001/2002
[speed] or
2007/2008
[frequency].
Final reference
limited by
2015/2017
[torque 1] or
2016/2018
[torque 2].
Final reference
limited by
4012/4013 [PID
set 1] or 4112/
4113 [PID set
2].
155