ABB DriveIT ACH550-01 User Manual page 356

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Diagnostics displays
The drive detects error situations and reports them using:
The green and red LED on the body of the drive.
The status LED on the control panel (if a HVAC control panel
is attached to the drive).
The control panel display (if a HVAC control panel is
attached to the drive).
The Fault Word and Alarm Word parameter bits (parameters
0305 to 0309.) See "Group 03: Actual Signals" .
The form of the display depends on the severity of the error. You
can specify the severity for many errors by directing the drive to:
Ignore the error situation.
Report the situation as an alarm.
Report the situation as a fault.
Red - faults
The drive signals that it has detected a severe error, or fault, by:
Enabling the red LED on the drive (LED is either steady or
flashing).
Setting an appropriate bit in a Fault Word parameter (0305 to
0307).
Overriding the control panel display with the display of a fault
code.
Stopping the motor (if it was on).
Sets an appropriate bit in Fault Word parameter 0305-0307.
The fault code on the control panel display is temporary.
Pressing any of the following buttons removes the fault
message: MENU, ENTER, UP button or DOWN button. The
message reappears after a few seconds if the control panel is
not touched and the fault is still active.
352
ACH550 User's Manual
Diagnostics and maintenance

Advertisement

Table of Contents
loading

This manual is also suitable for:

Driveit ach550-uh

Table of Contents