ABB DriveIT ACH550-01 User Manual page 348

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Parameter
name
42 External/ GAIN
Trimming
INTEGRATIO
PID
N TIME
DERIVATION
TIME
PID DERIV
FILTER
ERROR
VALUE INV
UNITS
UNIT SCALE
0% VALUE
100% VALUE
SET POINT
SEL
INTERNAL
SETPNT
SETPOINT
MIN
SETPOINT
MAX
FBK SEL
FBK
MULTIPLIER
ACT1 INPUT
ACT2 INPUT
ACT1
MINIMUM
ACT1
MAXIMUM
ACT2
MINIMUM
ACT2
MAXIMUM
ACTIVATE
OFFSET
TRIM MODE
TRIM SCALE
CORRECTIO
N SRC
344
HVAC
Default
Supply Fan Return Fan
ParIndex 1
2
4201
1.0
1.0
4202
60.0s
60.0s
4203
0.0s
0.0s
4204
1.0s
1.0s
4205
NO
NO
4206
%
%
4207
+0.0
+0.0
4208
0.0 %
0.0 %
4209
100.0 %
100.0 %
4210
INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL
4211
40.0 %
40.0 %
4212
0.0 %
0.0 %
4213
100.0 %
100.0 %
4214
ACT1
ACT1
4215
NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED
4216
AI2
AI2
4217
AI2
AI2
4218
0%
0%
4219
100%
100%
4220
0%
0%
4221
100%
100%
4228
NOT SEL
NOT SEL
4229
0.0 %
0.0 %
4230
NOT SEL
NOT SEL
4231
100.0 %
100.0 %
4232
PID2 REF
PID2 REF
ACH550 User's Manual
Cooling
Tower Fan Condenser
3
4
5
1.0
1.0
60.0s
60.0s
0.0s
0.0s
1.0s
1.0s
NO
NO
%
%
+0.0
+0.0
0.0 %
0.0 %
100.0 %
100.0 %
100.0 %
40.0 %
40.0 %
40.0 %
0.0 %
0.0 %
100.0 %
100.0 %
100.0 %
ACT1
ACT1
AI2
AI2
AI2
AI2
0%
0%
100%
100%
0%
0%
100%
100%
NOT SEL
NOT SEL
NOT SEL
0.0 %
0.0 %
NOT SEL
NOT SEL
NOT SEL
100.0 %
100.0 %
100.0 %
PID2 REF
PID2 REF
PID2 REF
Booster
Pump
6
1.0
1.0
60.0s
60.0s
0.0s
0.0s
1.0s
1.0s
NO
NO
%
%
+0.0
+0.0
0.0 %
0.0 %
100.0 %
40.0 %
0.0 %
0.0 %
100.0 %
ACT1
ACT1
AI2
AI2
AI2
AI2
0%
0%
100%
100%
0%
0%
100%
100%
NOT SEL
0.0 %
0.0 %
NOT SEL
100.0 %
PID2 REF