9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• Sets the maximum drive output voltage supplied to the motor.
• The ACH550 cannot supply the motor with a voltage greater than the
mains voltage.
Output voltage
P 9905
9906 MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: (0.2...2.0) · I
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
• Range: 10...500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
.
VOLT
• Field weakening point = Norm freq * Supply Volt / Mot Nom Volt
9908 MOTOR NOM SPEED
Defines the nominal motor speed.
• Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER
Defines the nominal motor power.
• Must equal the value on the motor rating plate.
Parameter listing and descriptions
Output
frequency
P 9907
(where I
N
200...600V, US:230...690V
type dependent
is drive current).
N
10.0...500 Hz
MOTOR NOM
50...18000 rpm
type dependent