Group 31: Automatic Reset
This group defines conditions for automatic resets. An automatic reset
occurs after a particular fault is detected. The drive holds for a set delay
time, then automatically restarts. You can limit the number of resets in a
specified time period, and you can set up automatic resets for a variety
of faults.
Code
Description
3101
NR OF TRIALS
Sets the number of allowed automatic resets within a trial period
defined by 3102
• If the number of automatic resets exceeds this limit (within the trial
time), the drive prevents additional automatic resets and remains
stopped.
• Starting then requires a successful reset performed from the control
panel or from a source selected by 1604
Example: Three faults have occurred in the trial time. The last is reset
only if the value for 3101
X
x = Automatic reset
3102
TRIAL TIME
Sets the time period used for counting and l
imiting the number of resets.
• See 3101
3103
DELAY TIME
Sets the delay time between a fault detection and attempted drive
restart.
• If
DELAY TIME
3104
AR OVERCURRENT
Sets the automatic reset for the
overcurrent function on or off.
0 =
DISABLE
1 =
ENABLE
• Automatically resets the fault (
3103
DELAY TIME
Parameter listing and descriptions
.
TRIAL TIME
NR OF TRIALS
Trial time
X X
.
NR OF TRIALS
= zero, the drive resets immediately.
– Disables automatic reset.
– Enables automatic reset.
, and the drive resumes normal operation.
Range
0...5
FAULT RESET SEL
is 3 or more.
Time
1.0...600.0 s
0.0...120.0 s
0=DISABLE,
1=ENABLE
) after the delay set by
OVERCURRENT
.