186 Technical data
The contacts of both relays are wired to a terminal block in the drive cubicle; see the
drive-specific circuit diagrams for details. The external voltage switched by the contacts is
to be connected to the same terminal block.

K3 contact data

Rated operational AC current (I
24...127 V, 50/60 Hz: 6 A
220...240 V, 50/60 Hz: 4 A
400...440 V, 50/60 Hz: 3 A
500 V, 50/60 Hz: 2 A
690 V, 50/60 Hz: 2 A
Rated making/breaking capacity (IEC/EN 60947-5-1 AC 15): 10 × I
Rated operational DC current (I
24 V DC: 6 A / 144 W
48 V DC: 2.8 A / 134 W
72 V DC: 1 A / 72 W
110 V DC: 0.55 A / 60 W
125 V DC: 0.55 A / 69 W
220 V DC: 0.27 A / 60 W
250 V DC: 0.27 A / 68 W
400 V DC: 0.15 A / 60 W
500 V DC: 0.13 A / 65 W
600 V DC: 0.1 A / 60 W
Rated short-time withstand current: 100 A for 1.0 s, 140 A for 0.1 s
Minimum switching capacity: 12 V / 3 mA

K62 contact data

Switching power: 3 VA or 3 W minimum, 2000 VA or 200 W maximum
Switching capacity, AC (IEC/EN 60947-5-1 AC 15):
NC: 230 V, 1 A
NO: 230 V, 3 A
Switching capacity, DC (IEC/EN 60947-5-1 DC 13):
NC / NO: 24 V, 2 A
Switching capacity (UL 508): R300

Efficiency

96.8 ... 98.6% at nominal power level depending on drive type
The efficiency is not calculated according to the ecodesign standard IEC 61800-9-2.
) (IEC/EN 60947-5-1 AC 15):
e
) (IEC/EN 60947-5-1 DC 13):
e
AC
e