Commissioning the override mode:
1.
Enter the parameters in all groups as needed, except group
17.
2.
Select the digital input that will activate override mode
P1701.
3.
Enter the frequency or speed reference for override mode,
P1702 and P1703, according to the motor control mode
P9904.
4.
Enter the pass code P1704 (358).
5.
Enable the override mode P1705.
Changing the override parameters:
1.
If override mode is already enabled, disable it:
Enter the pass code P1704.
Disable the override mode P1705.
2.
If needed, load the override parameter set P9902.
3.
Change the parameters as needed, except group 17.
4.
Change the parameters in group 17 as needed:
214
OVERSPEED
SERIAL 1 ERR
EFB CONFIG FILE
FORCE TRIP
EFB 1
EFB 2
EFB 3
MOTOR PHASE
PAR PFC REFNEG
PAR PFC IOCONF
PAR AI SCALE
PAR AO SCALE
PAR EXTROMISSING
PAR FBUSMISSING
PAR PFCWOSCALAR
Parameter listing and descriptions