Code
Description
1502
AO1 CONTENT MIN
Sets the
minimum content
value.
• Content is the
parameter
selected by
parameter
1501.
• Minimum value
refers to the
minimum
content value
that will be
converted to an
analog output.
• These
parameters
(content and
current min.
and max.
settings)
provide scale
and offset
adjustment for
the output. See
figure.
1503
AO1 CONTENT MAX
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be
converted to an analog output.
1504
MINIMUM AO1
Sets the minimum output current.
1505
MAXIMUM AO1
Sets the maximum output current.
1506
FILTER AO1
Defines the filter time constant for
• The filtered signal reaches 63% of a step change within the time
specified.
• See figure in parameter 1303.
1507
AO2 CONTENT
Defines the content for analog output
Parameter listing and descriptions
AO (mA)
P 1505 /
P 1511
P 1504 /
P 1510
P 1502 / 1508
AO (mA)
P 1505 /
P 1511
P 1504 /
P 1510
P 1503 / 1509
1.
AO
2. See
AO
Range
-
AO CONTENT
P 1503 / 1509
AO CONTENT
P 1502 / 1508
-
0.0...20.0 mA
0.0...20.0 mA
0.0...10.0 mA
99...199
1
above.
AO
CONTENT
205