ACH550 User's Manual
Control connection
Analog inputs
and outputs
Digital inputs
Relays (digital
outputs)
Cable
specifications
Appendix and available options
Control connection specifications
See table heading "Hardware description".
See footnote under table heading "Hardware
description".
• Max. contact voltage: 30 V DC, 250 AC
• Max. contact current/power: 6 A, 30 V D; 1500
VA, 250 VAC
• Max. continuous current: 2 A rms (cos = 1), 1 A
rms (cos =0.4)
• Minimum current:10 mA, 12 V DC
• Contact material: Silver-nickel (AgN)
• Isolation between relay digital outputs, test
voltage: 2.5 kV ms, 1 minute.
See "Control cables" in section "Preparing for
installation".
389