See table heading "Hardware description".
See footnote under table heading "Hardware
description".
• Max. contact voltage: 30 V DC, 250 AC
• Max. contact current/power: 6 A, 30 V D; 1500
VA, 250 VAC
• Max. continuous current: 2 A rms (cos = 1), 1 A
rms (cos =0.4)
• Minimum current:10 mA, 12 V DC
• Contact material: Silver-nickel (AgN)
• Isolation between relay digital outputs, test
voltage: 2.5 kV ms, 1 minute.
See "Control cables" in section "Preparing for
installation".