Code
Description
3622
BOOST SEL
Selects the source for the boost signal.
0=NOT SEL- Boost signal is disabled.
1=DI1-Defines DI1 as the boost signal.
2...6=DI2...DI6 - Defines DI2...DI6 as the boost signal.
-1=DI1(INV) - Defines an inverted digital input DI1 as the boost
signal.
-2...-6=Defines an inverted digital input DI2...DI6 as the boost
signal.
3623
BOOST TIME
Defines the boost ON time. Time is started when boost sel signal
is released. If parameter range is 01:30:00, then boost is active for
1 hour and 30 minutes after activation DI is released.
Boost active
Activation DI
3626
TIMER 1 SRC
Collects all wanted timers to a timer function.
0=NOT SEL- No timers have been selected..
1=P1- Time Period 1 selected in the timer.
2=P2- Time Period 2 selected in the timer.
3=P2 + P1 - Time Periods 1 and 2 selected in the timer.
4=P3 - Time Period 3 selected in the timer.
5=P3 + P1 - Time Periods 1 and 3 selected in the timer.
6=P3 + P2 - Time Periods 2 and 3 selected in the timer.
264
ACH550 User's Manual
Range
-6...6
00:00:00-23:59:58
Boost time
0...31
Parameter listing and descriptions