ACH550 User's Manual
History
For reference, the last three fault codes are stored into
parameters 0401, 0412, 0413. For the most recent fault
(identified by parameter 0401), the drive stores additional data
(in parameters 0402...0411) to aid in troubleshooting a problem.
For example, a parameter 0404 stores the motor speed at the
time of the fault.
To clear the fault history (all of Group 04, Fault History
parameters), follow these steps:
1.
In the control panel, Parameters mode, select parameter
0401.
2.
Press EDIT.
3.
Press the UP and DOWN buttons simultaneously.
4.
Press SAVE.
Correcting alarms
The recommended corrective action for alarms is:
Determine if the Alarm requires any corrective action (action
is not always required).
Use "Alarm listing" below to find and address the root cause
of the problem.
Alarm listing
The following table lists the alarms by code number and
describes each.
Alarm
Display
code
2001
Reserved
2002
2003
2004
DIR LOCK
Diagnostics and maintenance
Description
The change in direction being attempted is not
allowed. Either:
• Do not attempt to change the direction of motor
rotation, or
• Change parameter 1003
direction change (if reverse operation is safe).
to allow
DIRECTION
363