Code
Description
1609
START ENABLE 2
Selects the source of the start enable 2 signal.
Note: Start enable functionality differs from the run enable
functionality.
0 = NOT SEL - Allows the drive to start without an external start
enable signal.
1 = DI1 - Defines digital input DI1 as the start enable 2 signal. This
digital input must be activated for start enable 2 signal. If the voltage
drops and de-activates this digital input, the drive will coast to stop
and show alarm 2022 on panel display. The drive will not start until
start enable 2 signal resumes.
2...6 = DI2...DI6 - Defines digital input DI2...DI6 as the start
enable 2 signal. See DI1 above.
7 = COMM - Assigns the fieldbus Command Word as the
source for the start enable 2 signal. Bit 3 of the Command
word 2 (parameter 0302) activates the start disable 2 signal.
See fieldbus user's manual for detailed instructions.
(-1) = DI1(INV) - Defines an inverted digital input DI1 as the
start enable 2 signal.
(-2)...(-6) = DI2 (INV)...DI6(INV) - Defines an inverted digital
input DI2...DI6 as the start enable 2 signal.
See DI1 (INV) above.
212
ACH550 User's Manual
Range
-6...7
Parameter listing and descriptions