ACH550 User's Manual
Group 20: Limits
This group defines minimum and maximum limits to follow in driving the
motor – speed, frequency, current, torque, etc
Code
Description
2001
MINIMUM SPEED
Defines the minimum speed (rpm) allowed.
• A positive (or zero) minimum speed value defines two ranges, one
positive and one negative.
• A negative minimum speed value defines one speed range.
• See figure.
2002
MAXIMUM SPEED
Defines the maximum speed (rpm) allowed.
2003
MAX CURRENT
Defines the maximum output current
(A) supplied by the drive to the motor.
Parameter listing and descriptions
Speed
P 2002
Speed range allowed
0
P 2001
Speed
P 2002
Speed range allowed
P 2001
0
-(P 2001)
Speed range allowed
-(P 2002)
Range
-30000...30000 rpm
2001 value is< 0
Time
2001 value is > 0
Time
0...30000 rpm
(depends on drive
type)
217