ACH550 User's Manual
Group 21: Start/Stop
This group defines how the motor starts and stops. The ACH550
supports several start and stop modes.
Code
Description
2101
START FUNCTION
Selects the motor start method.
1 =
AUTO
VECTOR
function to a rotating axis and start at zero speed.
SCALAR
2 =
DC MAGN
Note! Mode cannot start a rotating motor.
Note! The drive starts when the set pre-magnetizing time (param.
2103) has passed, even if motor magnetization is not complete.
VECTOR
determined by the parameter 2103
current. The normal control is released exactly after the
magnetizing time. This selection guarantees the highest
possible break-away torque.
SCALAR SPEED
determined by the parameter 2103
current. The normal control is released exactly after the
magnetizing time.
3 =
SCALAR FLYSTART
VECTOR
SCALAR
correct output frequency to start a rotating motor. Useful if the
motor is already rotating and the drive will start smoothly at the
current frequency.
Parameter listing and descriptions
– Selects the automatic start mode.
control modes: Optimal start in most cases. Flying start
:
mode: Immediate start from zero frequency.
SPEED
– Selects the DC Magnetizing start mode.
control modes: Magnetizes the motor within the time
mode: Magnetizes the motor within the time
– Selects the flying start mode.
control modes: Not applicable.
control mode: The drive will automatically selects the
Range
1...5
using DC
DC MAGN TIME
using DC
DC MAGN TIME
221