Group 15: Analog Outputs
This group defines the drive's analog (current signal) outputs. The
drive's analog outputs can be:
Any parameter of the Operating Data group (Group 01).
Limited to programmable minimum and maximum values of output
current.
Scaled (and/or inverted) by defining the minimum and maximum
values of the source parameter (or content). Defining an maximum
value (parameter 1503 or 1509) that is less than the content
minimum value (parameter 1502 or 1508) results in an inverted
output.
Filtered
Code
Description
1501
AO1 CONTENT
Defines the content for analog output AO1.
99 =
EXCITE PTC
Output = 1.6 mA. See Group 35.
100 =
EXCITE PT
Output = 9.1 mA. See Group 35.
101...145 – Output corresponds to a parameter in the Operating Data
group (Group 01).
• Parameter defined by value (value 102 = parameter 0102)
204
– Provides a current source for sensor type PTC.
100 – Provides a current source for sensor type Pt100.
Parameter listing and descriptions
ACH550 User's Manual
Range
99...199