ABB DriveIT ACH550-01 User Manual page 243

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

ACH550 User's Manual
Code
Description
3003
EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an
external fault.
0 =
NOT SEL
1 =
1 – Defines digital input
DI
• Activating the digital input indicates a fault. The drive displays a
fault (14,
2...6 =
2...
DI
input.
• See
1 above.
DI
-1 =
1(
DI
INV
input.
• De-activating the digital input indicates a fault. The drive displays
a fault (14,
-2...-6 =
2(
DI
as the external fault input.
• See
1(
DI
3004
EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an
external fault.
• See parameter 3003 above.
3005
MOT THERM PROT
Defines the drive response to motor overheating.
0 =
NOT SEL
up.
1 =
– When the calculated motor temperature exceeds 90 C,
FAULT
displays a warning (2010,
motor temperature exceeds 110 C displays a fault (9,
OVERTEMP
2 =
WARNING
displays a warning (2010,
Parameter listing and descriptions
– External fault signal is not used.
DI
1) and the drive coasts to stop.
EXTERNAL FAULT
6 – Defines digital input
DI
) – Defines an inverted digital input
EXTERNAL FAULT
)...
6(
) – Defines an inverted digital input
INV
DI
INV
) above.
INV
– No response and/or motor thermal protection not set
MOT OVERTEMP
) and the drive coasts to stop.
– When the calculated motor temperature exceeds 90 C,
MOT OVERTEMP
Range
0...6, -1...-6
1 as the external fault input.
2...
6 as the external fault
DI
DI
1 as the external fault
DI
1) and the drive coasts to stop.
0...6,-1...-6
0...6, -1...-6
). When the calculated
).
2...
6
DI
DI
MOT
239