ABB DriveIT ACH550-01 User Manual page 176

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Group 01: Operating Data
This group contains drive operating data, including actual signals. The
drive sets the values for actual signals, based on measurements or
calculations. You cannot set these values.
Code Description
0102
SPEED
The calculated speed of the motor (rpm).
0103
OUTPUT FREQ
The frequency (Hz) applied to the motor. (Also shown by default in
OUTPUT display.)
0104
CURRENT
The motor current, as measured by the ACH550. (Also shown by
default in OUTPUT display.)
0105
TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor
nominal torque.
0106
POWER
The measured motor power in kW.
0107
DC BUS VOLTAGE
The DC bus voltage in VDC, as measured by the ACH550.
0109
OUTPUT VOLTAGE
The voltage applied to the motor.
0110
DRIVE TEMP
The temperature of the drive heatsink in Centigrade.
0111
EXTERNAL REF 1
External reference,
units determined by parameter 9904.
0112
EXTERNAL REF 2
External reference,
0113
CTRL LOCATION
Active control location. Alternatives are:
0 =
HAND
1 =
1
EXT
2 =
2
EXT
172
, in rpm or Hz –
1
REF
2, in %.
REF
Parameter listing and descriptions
ACH550 User's Manual
Range
0...30000 rpm
0.0...500.0 Hz
type dependent
-200...200%
type dependent
0...2.5*V
dN
0...2.0*V
dN
0...150ºC
0...300000 rpm/
0...500 Hz
0...100% (0...600% for
torque.
0=HAND, 1=EXT1,
2=EXT2