Auxiliary Circuit Current Consumption; Energy Efficiency Data (Ecodesign); Protection Classes; Ambient Conditions - ABB ACS880-7107LC Hardware Manual

Dc feeder units
Hide thumbs Also See for ACS880-7107LC:
Table of Contents

Advertisement

Auxiliary circuit current consumption

Auxiliary circuit current consumption varies depending on the actual drive configuration
and options. Contact ABB for the delivery-specific value.

Energy efficiency data (ecodesign)

Energy efficiency data is not provided for the drive/unit. Multidrives and multidrive
modules are not in the scope of the EU ecodesign requirements (Regulation
EU/2019/1781) or the UK ecodesign requirements (Regulation SI 2021 No. 745).

Protection classes

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL50)
Arcing class
(IEC TR 61641)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Installation site altitude
Air temperature
Relative humidity
IP42 (standard), IP54 (option +B055)
UL Type 1 (standard), UL Type 12 (option +B055). For indoor use only.
B – ASSEMBLY providing personnel and ASSEMBLY protection under arcing
conditions.
Tested at the following voltage with an arcing current of 65 kA for 300 milli-
seconds:
• 400 V units (indicated by "-3" in drive type): 420 V
• 500 V units (indicated by "-5" in drive type): 550 V
• 690 V units (indicated by "-7" in drive type): 760 V
III, except for auxiliary power connections (fan, control, heating, lighting,
cooling unit pump etc) which are category II.
I
Operation
installed for stationary
use
0...2000 m (0...6562 ft)
above sea level. For alti-
tudes over 2000 m, con-
tact ABB.
Output derated above
1000 m (3281 ft).
0 ... +45 °C
(+32 ... +113 °F), no con-
densation allowed. Out-
put derated in the range
+45 ... +55 °C
(+113 ... +131 °F).
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
Storage
in the protective pack-
age
-
-40 ... +70 °C
(-40 ... +158 °F)
Max. 95%
presence of corrosive gases.
Technical data 61
Transportation
in the protective pack-
age
-
-40 ... +70 °C
(-40 ... +158 °F)
Max. 95%

Advertisement

Table of Contents
loading

Table of Contents