ABB DriveIT ACH550-01 User Manual page 362

Hide thumbs Also See for DriveIT ACH550-01:
Table of Contents

Advertisement

Fault
Fault name in
code
panel
31
1
EFB
32
2
EFB
33
3
EFB
34
MOTOR PHASE
35
OUTP WIRING
101
SYSTEM
ERROR
102
SYSTEM
ERROR
103
SYSTEM
ERROR
104
SYSTEM
ERROR
105
SYSTEM
ERROR
358
Description and recommended
corrective action
Fault code reserved for the EFB protocol
application. The meaning is protocol
dependent.
Fault code reserved for the EFB protocol
application. The meaning is protocol
dependent.
Fault code reserved for the EFB protocol
application. The meaning is protocol
dependent.
Fault in the motor circuit. One of the motor
phases is lost. Check for and correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
Error in power wiring suspected. Check for
and correct:
• Input power wired to drive output.
• Ground faults.
Error internal to the drive. Contact your local ABB
sales representative and report the error number.