Connecting Cables; Connecting The Fieldbus - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

765-1205/100-000
U = 2 × I × R
where:
U
2
I
R
L
For WAGO 4 × 1.5 mm
Example of Voltage Drop for Feed and Return Lines with a Current of 8 A on the
WAGO 4 × 1.5 mm
U = 2 × 8 A × 13.7 Ω/km = 219.2 V/km
This corresponds to a voltage drop of 2.19 V per 10 m of cable length for feed and return
lines.
Example of Voltage Drop per Wire with a Current of 16 A on a 4 × 2.5 mm
Cable
U = 2 × 16 A × 8.22 Ω/km = 263 V/km
This corresponds to a voltage drop of 2.63 V per 10 m of cable length.
If the resistance of the cable used is not known, it can be calculated approximately with
the following formula:
R
= l / (K × A)
L
where:
R
L
I
K
A

9.3 Connecting Cables

WAGO recommends using 765 Series connecting cables, pluggable connectors and ac-
cessories for 756 Series products, which have been tailored specifically to the WAGO I/O
System Field.
The tightening torques given in section
pluggable connectors of the connecting cables.

9.4 Connecting the Fieldbus

To establish a connection to an EtherCAT
to an EtherCAT
To establish a connection to an IO controller, connect the product to a network with a
transmission rate of 100 Mbit/s in full duplex operation.
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Voltage drop
Factor for feed and return lines
Current
Cable resistance
2
supply cables, the cable resistance R
2
Supply Cable
Cable resistance
Cable length
Specific cable resistance of the conductor material (usually copper) according to manufacturer's
specifications
Cable cross-section
®
network.
per wire R
L
8 Connection Technology [} 18]
®
master, it is necessary to connect the module
Connection
≤ 13.7 Ω/km.
L
2
Supply
apply to the
51

Advertisement

Table of Contents
loading

Table of Contents