Configuration Software; Starting Up Devicenet Fieldbus Nodes; Connecting The Pc And Fieldbus Node; Setting The Mac Id And Baud Rate - WAGO 750-306 Technical Description

Modular i/o system devicenet
Hide thumbs Also See for 750-306:
Table of Contents

Advertisement

3.1.6 Configuration Software

To enable a connection between the PLC and the fieldbus devices, the inter-
face modules have to be configured with the individual station data.
To this effect, the scope of delivery of WAGO-I/O-SYSTEM 758 includes the
WAGO NETCON software intended for design and configuration, start-up and
diagnosis.
Further configuration software of different manufacturers include, for in-
stance, RSNetWorx.

3.1.7 Starting up DeviceNet Fieldbus Nodes

This chapter shows the step-by-step procedure for starting up a
WAGO DeviceNet fieldbus node.
Attention
This description is given as an example and is limited to the execution of a
local start-up of an individual DeviceNet fieldbus node.
The procedure contains the following steps:

1. Connecting the PC and fieldbus node

2. Setting the MAC ID and baud rate

3. Configuration with static Assembly
3.1.7.1 Connecting the PC and Fieldbus Node
1. Connect the fitted DeviceNet fieldbus node to the DeviceNet fieldbus
2. Start your PC.
3.1.7.2 Setting the MAC ID and Baud Rate
1. Use the DIP switches 1...6 to set the desired node address (MAC ID). The
Fig. 3-10: Example: Setting the
MAC ID 4 (DIP 3 = ON).
WAGO-I/O-SYSTEM 750
DeviceNet
PCB in your PC via a fieldbus cable.
The 24 V field bus supply is fed by an external fieldbus network power
supply over the connections V+, V- of the 5-pin fieldbus connector (MCS
Series 231).
binary significance of the individual DIP switches increases according to
the switch number.
g012443x
Fieldbus Coupler/Controller • 51
Fieldbus Coupler 750-306
DIP switch
Value
1
0
2
2
1
2
3
2
2
4
3
2
5
4
2
6
5
2