Connecting The Power Supply To A B&R Device; Functional Ground - Grounding Concept - B&R Panel PC 2100 User Manual

Hide thumbs Also See for Panel PC 2100:
Table of Contents

Advertisement

Commissioning
3.2.2 Connecting the power supply to a B&R device
Danger!
The power supply to the B&R device must be completely interrupted. Before connecting the power
cable, it is necessary to check whether it has been disconnected from the power source (e.g. power
supply).
1. Discharge any electrostatic charge on the housing or ground connection.
2. Connect the power supply connector to the B&R device and tighten the mounting screws (max. tightening
torque 0.5 Nm).

3.2.3 Functional ground - Grounding concept

Functional ground is a current path of low impedance between electrical circuits and ground. It is used to improve
immunity to interference, for example, and not necessarily as a protective measure. It therefore serves only to
conduct interference, not to provide any kind of protection against electric shock.
This device comes equipped with 2 functional ground connections:
• Functional ground connection for the power supply
• Ground connection
To ensure the safe conductance of electrical interference, the following points must be observed:
• Connect the device to the central grounding point (e.g. the control cabinet or the system) using the shortest
path with the lowest resistance.
• A cable with a minimum cross section of 2.5 mm² per connection must be used. If a cable with wire end
sleeves is connected to terminal block 0TB103.9 or 0TB103.91, then a cable with maximum 1.5 mm² per
connection is possible.
• Observe the line shielding concept. All data cables connected to the device must be shielded.
The following symbol is used to indicate functional ground on the B&R device:
222
Figure 125: Connecting the power supply connector to a B&R device
Panel PC 2100 user's manual V1.17