Technical data
7
8
9
10
1)
The interfaces, etc. available on the device or module have been numbered as such for the purpose of clear differentiation. This numbering may deviate
from the numbering used by the respective operating system, however.
2)
This interface can only be used in Automation Runtime and is referred to as IF7 in Automation Studio / Automation Runtime. It is not a "PC interface" and
therefore not shown in BIOS.
The RTS line must be switched by the driver for each transmission or reception; there is no automatic switch-
back mechanism.
The voltage drop resulting from long cable lengths can result in greater potential differences between the bus
stations, which can hinder communication. This can be improved by running the ground wire with the others.
2.3.5.2.3.3 RS485 - Bus length and cable type
The maximum transfer rate of 115 kbit/s depends on the cable length as well as the type of cable being used.
Extension
1200 m
The material used for the cable should have all of the following properties or deviate from them as little as possible
to achieve an optimal transfer rate.
RS485 cables
Signal lines
Cable cross section
Wire insulation
Conductor resistance
Stranding
Shield
Ground line
Cable cross section
Wire insulation
Conductor cross section
Outer jacket
Material
Properties
Complete shielding
2.3.5.2.3.4 CAN bus interface - Pinout
The CAN bus interface on the system unit is referred to as IFx.
The CAN bus interface is a 10-pin female connector without electrical isolation.
Transfer rate
Bus length
Pin
1
2
3
4
5
6
7
8
9
10
1)
The interfaces, etc. available on the device or module have been numbered as such for the purpose of clear differentiation. This numbering may deviate
from the numbering used by the respective operating system, however.
2)
This interface can only be used in Automation Runtime and is referred to as IF3 in Automation Studio / Automation Runtime. It is not a "PC interface" and
therefore not shown in BIOS.
168
Serial interface COM - IFx
-
COM GND
DATA\
DATA
Table 133: 5ACCIF01.FPCS-000 - COM interface
Table 134: RS485 - Bus length and transfer rate
4x 0.25 mm² (24 AWG / 19), tinned copper stranded wire
1x 0.34 mm² (22 AWG / 19), tinned copper stranded wire
Table 135: RS485 - Cable requirements
CAN bus - IFx
Max. 1 Mbit/s
Max. 1000 m
Assignment
-
Shield
-
-
CAN H
CAN L
CAN GND
-
-
-
Table 136: 5ACCIF01.FPCS-000 - CAN bus interface
1)2)
Transfer rate
Typ. 115 kbit/s
Property
PE
≤82 Ω/km
Wires stranded in pairs
Paired shield with aluminum foil
PE
≤59 Ω/km
PUR compound
Halogen-free
Composed of tinned copper wires
1)2)
10-pin, male
1
3
2
4
Panel PC 2100 user's manual V1.17
5
7
9
6
8 10