Technical data

2.3.5 Interface options

Information:
It is important to note that not every interface option can be connected in interface slots IF1 and IFx.
For more information, see section
Information:
Interface options can only be installed and replaced by B&R.

2.3.5.1 5ACCIF01.FPCC-000

2.3.5.1.1 General information
Interface option 5ACCIF01.FPSC-000 is equipped with a POWERLINK interface, 2 CAN bus master interfaces
and an X2X Link master interface. 512 kB of nvSRAM is also installed.
• 1x POWERLINK interface for managing or controlled node
• 2x CAN bus master interfaces
• 1x X2X Link master interface
• 512 kB nvSRAM
• Compatible with APC2100/PPC2100 and APC2200/PPC2200
This interface option can only be operated with Automation Runtime.
2.3.5.1.2 Order data
Model number
Short description
Interface options
5ACCIF01.FPCC-000
Interface card - 2x CAN interfaces - 1x X2X Link interface -
1x POWERLINK interface - 512 kB nvSRAM - For APC2100/
PPC2100/APC2200/PPC2200 - Only available with a new de-
vice
Optional accessories
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange
2.3.5.1.3 Technical data
Information:
The following specifications, properties and limit values apply only to this accessory and may deviate
from those that apply to the complete system. For the complete system in which this accessory is
installed, for example, the data specified for that complete system applies.
Model number
General information
LED status indicators
B&R ID code
Certifications
CE
UL
HazLoc
DNV GL
158
"IF option slot (IF1, IFx)" on page
Table 112: 5ACCIF01.FPCC-000 - Order data
Table 113: 5ACCIF01.FPCC-000 - Technical data
56.
5ACCIF01.FPCC-000
L1, L2, L3
0xE9BD
Yes
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (Bridge and open deck)