Parameter
Pr.
82
90
91
92
93
94
859
Tab. 6-22: Setting of parameter 82, 90 to 94 and 859
Refer to the following table and set Pr. 83 and Pr. 84.
Pr.
Name
83
Rated motor voltage
84
Rated motor frequency
Tab. 6-23: Setting of parameter 83 and 84
NOTE
When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants are used.
FR-E700 SC EC/ENE
Name
Motor excitation current
(no load current)
Motor constant R1
Motor constant R2
Motor constant L1
Motor constant L2
Motor constant X
Torque current
Setting Range
Setting Increments
0–500 A, 9999
0–50 , 9999
0.001
0–50 , 9999
0.001
0–1000 mH, 9999
0.1 mH
0–1000 mH, 9999
0.1 mH
0–100%, 9999
0–500 A, 9999
Setting Range
0–1000 V
10–120 Hz
Selection and protection of a motor
Initial Value
0.01 A
9999
9999
9999
9999
9999
0.1%
9999
0.01 A
9999
Setting Increments
Initial Value
0.1 V
0.01 Hz
400 V
50 Hz
6 - 99