Mitsubishi Electric FR-E700 Instruction Manual page 161

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
DU/PU main display data
52
selection
AM terminal function
158
selection
Watt-hour meter clear
170
Operation hour meter clear
171
Monitor decimal digits
268
selection
Energizing time
563
carrying-over times
Operating time
564
carrying-over times
Tab. 6-1:
Parameter overview (7)
FR-E700 SC EC/ENE
Incre-
Initial
Setting
ments
Value
Range
0/5/7–12/
14/20/23–25/
1
0
52–57/61/62/
100
1–3/5/7–12/
1
1
14/21/24/52/
53/61/62
0
1
9999
10
9999
1
9999
0/9999
0
1
9999
1
9999
1
0
0–65535
1
0
0–65535
Description
Selects monitor to be displayed on the
operation panel and parameter unit and
monitor to be output to the terminal AM.
0:
Output frequency (Pr. 52)
1:
Output frequency (Pr. 158)
2:
Output current (Pr. 158)
3:
Output voltage (Pr. 158)
5:
Frequency setting value
7:
Motor torque
8:
Converter output voltage
9:
Regenerative brake duty
10: Electronic thermal relay
function load factor
11: Output current peak value
12: Converter output voltage
peak value
14: Output power
20: Cumulative energization
time (Pr. 52)
21: Reference voltage output
(Pr. 158)
23: Actual operation time (Pr. 52)
24: Motor load factor
25: Cumulative power (Pr. 52)
52: PID set point
53: PID measured value
54: PID deviation (Pr. 52)
55: I/O terminal status (Pr. 52)
56: Option input terminal status
(Pr. 52)
57: Option output terminal status
(Pr. 52)
61: Motor thermal load factor
62: Inverter load factor
100: Set frequency is displayed
during a stop and output
frequency is displayed during
operation (Pr. 52).
Set "0" to clear the watt-hour meter
monitor.
Set the maximum value when monitoring
from communication to 0 to 9999 kWh.
Set the maximum value when monitoring
from communication to 0 to 65535 kWh.
Set "0" in the parameter to clear the watt
hour monitor.
Setting "9999" has no effect.
Displays the monitor as integral value.
Displays the monitor in increments of 0.1.
No fixed decimal position
The numbers of cumulative energizing time
monitor exceeded 65535 h is displayed.
Reading only
The numbers of operation time monitor
exceeded 65535 h is displayed.
Reading only
Parameter overview
All
Para-
Para-
Para-
meter-
meter
meter
Copy
Clear
Refer
Clear
to
Page
✔: Enabled
—: Disabled
6-140
6 - 7