Mitsubishi Electric FR-E700 Instruction Manual page 424

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Communication operation and setting
Example
To read the register values of 41004 (Pr. 4) to 41006 (Pr. 6) from the slave address 17 (H11).
Query message
Slave Address
H11
(8 bits)
Normal response (Response message)
Slave Address
H11
(8 Bits)
Read value:
Register 41004 (Pr. 4): H1770 (60.00 Hz)
Register 41005 (Pr. 5): H0BB8 (30.00 Hz)
Register 41006 (Pr. 6): H03E8 (10.00 Hz)
6 - 270
Function
Starting Address
H03
H03
(8 bits)
(8 bits)
(8 bits)
Function
Byte Count
H03
H06
H17
(8 Bits)
(8 Bits)
(8 Bits)
No. of Points
HEB
H00
H03
(8 bits)
(8 bits)
Data
H70
H0B
HB8
(8 Bits)
(8 Bits)
(8 Bits)
Parameter
CRC Check
H77
H2B
(8 bits)
(8 bits)
CRC Check
H03
HE8
H2C
HE6
(8 Bits)
(8 Bits)
(8 Bits)
(8 Bits)