Simple mode parameter list
5.1.2

When the rated motor frequency is 60 Hz (Pr. 3)

First, check the motor rating plate. If a frequency given on the rating plate is "60 Hz" only, always set
Pr. 3 "Base frequency" to "60 Hz". Leaving the base frequency unchanged from "50 Hz" may make the
voltage low and the torque insufficient. It may result in an inverter trip due to overload.
Pr. No. Name
3
Base frequency
Example
Change Pr. 3 "Base frequency" to 60 Hz according to the motor rated frequency.
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.3 (Pr. 3) appears.
Press the SET key to show the currently set value.
The initial value "50.00" appears.
Turn the digital dial to change it to the setting
value of "60.00".
Press the SET key to set.
By turning the digital dial, you can read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
Fig. 5-2:
5 - 4
Initial Value
50 Hz
Operation
Setting the base frequency
V/F
V/F
V/F
Setting
Description
Range
0–400 Hz
Set the rated motor frequency.
The parameter number
read previously appears.
Flicker ... Parameter setting complete!
Basic settings
Display
PU indication is lit.
PRM indication is lit.
I001745E