Useful Functions; Cooling Fan Operation Selection (Pr. 244) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
6.21

Useful functions

Purpose
To determine the maintenance time of
parts.
Freely available parameter
Increase cooling fan life
6.21.1

Cooling fan operation selection (Pr. 244)

You can control the operation of the cooling fan (FR-E720S-050SC or more, FR-E740-040SC or more)
built in the inverter.
Pr. No.
Name
Cooling fan operation
244
selection
The above parameter can be set when Pr. 160 "User group read selection" = 0.
In either of the following cases, fan operation is regarded as faulty, "FN" is shown on the operation
panel, and the fan fault "FAN" and alarm "LF" signals are output.
Pr. 244 = "0"
When the fan comes to a stop with power on.
Pr. 244 = "1"
When the fan stops during the fan ON command while the inverter is running.
For the terminal used for FAN signal output, set "25" (source logic) or "125" (sink logic) to any of Pr. 190
to Pr. 192 "Output terminal function selection", and for the LF signal, set "98" (source logic) or "198"
(sink logic).
NOTE
When terminal assignment is changed using Pr. 190 to Pr. 192 "Output terminal function selec-
tion", the other functions may be affected. Please make setting after confirming the function of
each terminal.
FR-E700 SC EC/ENE
Parameters that must be set
Cooling fan operation selection
Inverter part life display
Maintenance output function
Current average value monitor signal
Free parameter
Setting
Initial Value
Description
Range
Operates at power on
0
Cooling fan on/off control invalid (The cooling fan
is always on at power on)
Cooling fan on/off control valid
1
The fan is always on while the inverter is running.
1
During a stop, the inverter status is monitored
and the fan switches on-off according to the
temperature of the heatsink.
Useful functions
Refer to
Section
Pr. 244
6.21.1
Pr. 255–Pr. 259
6.21.2
Pr. 503–Pr. 504
6.21.3
Pr. 555–Pr. 557
6.21.4
Pr. 888–Pr. 889
6.21.5
Parameters referred to
190–192 Output terminal
function selection
Refer to
Section
6.10.5
6 - 317