Operation selection at power failure
Pr. No. Name
Regenerative function
30
selection
57
Restart coasting time
58
Restart cushion time
96
Auto tuning setting/status
Automatic restart after
162
instantaneous power failure
selection
Stall prevention operation
165
level for restart
298
Frequency search gain
Rotation direction detection
299
selection at restarting
611
Acceleration time at a restart
The above parameters can be set when Pr. 160 "User group read selection" = 0.
6 - 154
Initial Value
Setting Range
Description
The motor starts at the starting frequency when
0/1
MRS (X10) turns on then off.
0
Restart operation is performed when MRS (X10)
2
turns on then off
FR-E720S-080SC or less,
FR-E740-040SC or less.................................... 1 s
0
FR-E720S-110SC,
FR-E740-060SC to 170SC................................ 2 s
FR-E740-230SC and 300SC............................. 3 s
9999
Set the waiting time for inverter-triggered restart
0.1–5 s
after an instantaneous power failure.
9999
No restart
1s
0–60 s
Set a voltage starting time at restart.
0
Offline auto tuning is not performed
Advanced magnetic flux vector control
Offline auto tuning is performed without motor
1
running (all motor constants) (Refer to section
6.3.2.)
For general-purpose magnetic flux vector control
0
Offline auto tuning is performed without motor
11
running (motor constants (R1) only)
(Refer to section 6.3.3.)
Offline auto tuning (tuning performed without
motor running) for V/F control and automatic
21
restart after instantaneous power failure (with
frequency search)
0
With frequency search
No frequency search:
The output voltage is increased until the preset
1
frequency is reached, irrespective of the current
motor speed.
0
10
Frequency search at every start
On every start the output voltage is increased until
11
the preset frequency reached, irrespective of the
current motor speed.
Consider the rated inverter current according to the
overload capacity as 100% and set the stall
150%
0–200%
prevention operation level during restart
operation.
When offline auto tuning is performed under V/F
control, frequency search gain necessary for
0–32767
frequency search for automatic restart after
instantaneous power failure is set as well as the
9999
motor constants (R1).
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
9999
SF-HRCA) constants
0
Without rotation direction detection
1
With rotation direction detection
9999
When Pr. 78 = "0", the rotation direction is
detected.
9999
When Pr. 78 = "1","2", the rotation direction is not
detected.
Acceleration time to reach the acceleration time
0–3600 s
reference frequency at a restart.
9999
Acceleration time for restart is the normal
9999
acceleration time (e.g. Pr. 7)
Parameter
Refer to
Parameters referred to
Section
7
Acceleration time
6.7.1
21
Acceleration/
6.7.1
deceleration time
increments
13
Starting frequency
6.7.2
65
Retry selection
6.13.1
67–69
Retry function
6.13.1
71
Applied motor
6.8.2
78
Reverse rotation
6.17.3
prevention selection
178–184
Input terminal function
6.10.1
selection