Mitsubishi Electric FR-E700 Instruction Manual page 432

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Communication operation and setting
Definition
Bit
Control Input Instruction
0
Stop command
1
Forward rotation command
2
Reverse rotation command
3
RH (high speed operation command)
4
RM (middle speed operation command)
5
RL (low speed operation command)
6
0
7
RT (second function selection)
8
AU (current input selection)
9
0
10
MRS (output stop)
11
0
12
RES (reset)
13
0
14
0
15
0
Tab. 6-101: Inverter status/control input instruction
The signal within parentheses is the default setting. The description changes depending on the
setting of Pr. 180 to Pr. 184 "Input terminal function selection". (Refer to section 6.10.1.) Each
assigned signal is valid or invalid depending on NET. (Refer to section 6.18.3.)
The signal within parentheses is the default setting. Definitions change according to the Pr. 190
to Pr. 192 "Output terminal function selection". (Refer to section 6.10.5.)
Operation Mode
EXT
PU
EXT JOG
PU JOG
NET
PU + EXT
Tab. 6-102: Operation mode/inverter setting
The restrictions depending on the operation mode changes according to the computer link
specifications.
6 - 278
Inverter Status
RUN (inverter running)
Forward rotation
Reverse rotation
SU (up to frequency)
OL (overload)
0
FU (frequency detection)
ABC (Alarm)
0
0
0
0
0
0
0
Alarm
Read Value
H0000
H0001
H0002
H0003
H0004
H0005
Parameter
Written Value
H0010
H0014