Connection Of The High Power Factor Converter Fr-Hc - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Wiring
3.8.4

Connection of the high power factor converter FR-HC

When connecting the high power factor converter (FR-HC) to suppress power harmonics, perform
wiring securely as shown below.
CAUTION:
E
Perform wiring of the high power factor converter (FR-HC) securely as shown below. Incorrect
connection will damage the high power factor converter and inverter.
3-phase AC
power supply
Fig. 3-39: Connection of the high power factor converter FR-HC
Keep input terminals (R/L1, S/L2, T/L3) open. Incorrect connection will damage the inverter.
Do not insert an MCCB between the terminals P/+ and N/ (between P and P/+, between N and
N/ ). Opposite polarity of terminals N/ , P/+ will damage the inverter.
Use Pr. 178 to Pr. 184 "Input terminal function selection" to assign the terminals used for the X10,
RES signal. (Refer to section 6.10).
Be sure to connect terminal RDY of the FR-HC to the X10 signal or MRS signal assigned terminal
of the inverter, and connect terminal SE of the FR-HC to terminal SD of the inverter. Without proper
connecting, FR-HC will be damaged.
NOTES
The voltage phases of terminals R/L1, S/L2, T/L3 and terminals R4, S4, T4 must be matched.
Use sink logic when the FR-HC is connected. The FR-HC cannot be connected when source logic
(factory setting) is selected.
Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
FR-E700 SC EC/ENE
External box
(FR-HCB)
Reactor 1
(FR-HCL01)
Connection of stand-alone option units
High power factor
converter (FR-HC)
Reactor 2
(FR-HCL02)
Phase
detection
Inverter
Motor
M
3~
I002060E
3 - 45