Connection Of A Dedicated External Brake Resistor Fr-Abr (Fr-E720S-030Sc Or More, Fr-E740-016Sc Or More) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Wiring
3.8.2
Connection of a dedicated external brake resistor FR-ABR
(FR-E720S-030SC or more, FR-E740-016SC or more)
Install a dedicated brake resistor (FR-ABR) outside when the motor is made to run by the load, quick
deceleration is required, etc. Connect a dedicated brake resistor (FR-ABR) to terminal + and PR (resp.
P/+ and PR). (For the locations of terminal + and PR (resp. P/+ and PR), refer to the terminal block layout
(section 3.3.2).)
Set parameters below (refer to section 6.9.2).
Connected Brake
Resistor
FR-ABR
Tab. 3-20: Setting of parameter 30 and 70 when connecting an external brake resistor
CAUTION:
E
● The brake resistor connected should only be the dedicated brake resistor.
● Do not remove a jumper across terminal + and P1 (resp. P/+ and P1) except when connecting
a DC reactor.
● The shape of jumper differs according to capacities.
FR-E720S-030SC
FR-E700 SC EC/ENE
Pr. 30 "Regenerative
function selection"
1
Jumper
Terminal +
Brake resistor
Connection of stand-alone option units
Parameter Setting
Pr. 70 "Special regenerative brake duty"
FR-E720S-110SC or less
FR-E740-170SC or less
FR-E740-230SC or more
Fig. 3-31:
Connection of a brake resistor to the terminals +
and PR for the inverter FR-E720S-030SC
Terminal PR
10 (%)
6 (%)
I002036E