Mitsubishi Electric FR-E700 Instruction Manual page 300

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Monitor display and monitor output signals
Cumulative energizing power monitor and clear (Pr. 170)
On the cumulative power monitor (Pr. 52 = "25"), the output power monitor value is added up and is
updated in 1h increments. The operation panel, parameter unit (FR-PU04/FR-PU07) and communi-
cation (RS-485 communication, communication option) display increments and display ranges are as
indicated below:
Operation Panel
Range
0–99.99 kWh
100–999.9 kWh
1000–9999 kWh
Tab. 6-38: Units and range of the cumulative energizing monitor
Power is measured in the range 0 to 9999.99 kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in
0.1 kWh increments.
Power is measured in the range 0 to 99999.99 kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in
0.1 kWh increments.
Writing "0" to Pr. 170 clears the cumulative energizing power monitor.
NOTE
If "0" is written to Pr. 170 and Pr. 170 is read again, "9999" or "10" is displayed.
Cumulative energizing time and actual operation time monitor (Pr. 171, Pr. 563, Pr. 564)
Cumulative energization time monitor (Pr. 52 = "20") accumulates energization time from shipment
of the inverter every one hour.
On the actual operation time monitor (Pr. 52 = "23"), the inverter running time is added up every hour.
(Time is not added up during a stop.)
If the monitored value exceeds 65535, it is added up from 0. You can check the numbers of cumulative
energization time monitor exceeded 65535 h with Pr. 563 and the numbers of actual operation time
monitor exceeded 65535 h with Pr. 564.
Writing "0" to Pr. 171 clears the cumulative energization power monitor. (The cumulative time mon-
itor can not be cleared.)
NOTES
The actual operation time is not added up unless the inverter is operated one or more hours con-
tinuously.
If "0" is written to Pr. 171 and Pr. 171 is read again, "9999" is always displayed. Setting "9999" does
not clear the actual operation time meter.
6 - 146
FR-PU04/FR-PU07
Unit
Range
0.01 kWh
0–999.99 kWh
0.1 kWh
1000–9999.9 kWh
1 kWh
10000–99999 kWh
Communication
Range
Unit
Pr. 170 = 10
0.01 kWh
0.1 kWh
0–9999 kWh
1 kWh
Parameter
Unit
Pr. 170 = 9999
0–65535 kWh
1 kWh
(initial value)