Mitsubishi Electric FR-E700 Instruction Manual page 505

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
I/O signal list
● When Pr. 544 = "0" (compatible with CC-Link Ver.1)
– Remote I/O (32 points)
Device
Signal
No.
RYn0
Forward rotation command
RYn1
Reverse rotation command
High-speed operation command
RYn2
(terminal RH function)
Middle-speed operation command
RYn3
(terminal RM function)
Low-speed operation command
RYn4
(terminal RL function)
RYn5
Not used
RYn6
Second function selection (RT signal)
RYn7
Terminal 4 input selection (AU signal)
RYn8
Not used
RYn9
Output stop (terminal MRS function)
RYnA
Not used
RYnB
Reset (terminal RES function)
RYnC
Monitor command
RYnD
Frequency setting command (RAM)
RYnE
Frequency setting command (RAM, E²PROM)
RYnF
Instruction code execution request
RY(n+1)0
to
Reserved
RY(n+1)7
RY(n+1)8 Not used (initial data process completion flag)
RY(n+1)9 Not used (initial data process request flag)
RY(n+1)A Error reset request flag
RY(n+1)B
to
Reserved
RY(n+1)F
Tab. 6-144:
Remote outputs
These signals are set in the initial status. Using Pr. 180 to Pr. 184, you can change input signal
functions. For the details of Pr. 180 to Pr. 184, refer to page 6-116.
The signals are fixed. They cannot be changed using parameters.
These signals are set in the initial status. Using Pr. 190 to Pr. 192, you can change output signal
functions. For the details of Pr. 190 to Pr. 192 refer to page 6-126.
Functions assigned to Pr. 313 to Pr. 315 are activated. For the assignable functions, refer to the
description of Pr. 190 to Pr. 192 on page 6-126.
"n" indicates a value determined according to the station number setting.
FR-E700 SC EC/ENE
Device
Refer to
Signal
page
No.
RXn0
Forward running
6-356
RXn1
Reverse running
6-356
RXn2
Inverter running (terminal RUN function)
6-356
RXn3
Up to frequency (SU signal)
RXn4
6-356
Overload alarm (OL signal)
RXn5
Not used
6-356
RXn6
Frequency detection (terminal FU function)
RXn7
Fault (terminal ABC function)
6-356
RXn8
Not used
6-356
RXn9
Pr. 313 assignment function (DO0)
RXnA
Pr. 314 assignment function (DO1)
6-356
RXnB
Pr. 315 assignment function (DO2)
RXnC
Monitoring
6-356
RXnD
Frequency setting completion (RAM)
RXnE
Frequency setting completion (RAM, E²PROM)
6-356
RXnF
Instruction code execution completion
6-356
6-356
RX(n+1)0
to
Reserved
6-356
RX(n+1)7
RX(n+1)8 Not used (initial data process request flag)
RX(n+1)9 Not used (initial data process completion flag)
RX(n+1)A Error status flag
6-356
6-356
RX(n+1)B Remote station ready
6-356
RX(n+1)C
to
Reserved
RX(n+1)F
Tab. 6-145:
CC-Link IE Field Network Basic
Remote inputs
Refer to
page
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6-357
6 - 351