Selection of operation mode and operation location
6.18.2

Operation mode at power on (Pr. 79, Pr. 340)

When power is switched on or when power comes back on after instantaneous power failure, the
inverter can be started up in network operation mode.
After the inverter has started up in the network operation mode, parameter write and operation can
be performed from a program.
Set this mode for communication operation using the inverter RS-485 terminals or communication
option.
Pr. No. Name
79
Operation mode selection
Communication start-up
340
mode selection
The above parameters can be changed during a stop in any operation mode.
The above parameter can be set when Pr. 160 "User group read selection" = 0. However, the
parameters can be set whenever the communication option is connected. (Refer to section
6.17.4.)
6 - 218
Setting
Initial Value
Description
Range
Select the operation mode.
0
0–4/6/7
(Refer to page 6-209)
0
As set in Pr. 79.
1
Started in network operation mode.
0
Started in network operation mode. Operation mode
10
can be changed between the PU operation mode and
network operation mode from the operation panel.
Parameter
Parameters referred to
79 Operation mode selection 6.18.1
Refer to
Section