Acceleration and deceleration pattern (Pr. 29)

You can set the acceleration/deceleration pattern suitable for application.
Pr. No. Name
Acceleration/deceleration
29
pattern selection
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Linear acceleration/deceleration (Pr. 29 = "0", initial value)
For the inverter operation, the output frequency is made to change linearly (linear acceleration/de-
celeration) to prevent the motor and inverter from excessive stress to reach the set frequency during
acceleration, deceleration, etc. when frequency changes. Linear acceleration/deceleration has a uni-
form frequency/time slope (refer to 6-33).
FR-E700 SC EC/ENE
Setting
Initial Value
Description
Range
0
Linear acceleration/deceleration
1
S-pattern acceleration/deceleration A
0
2
S-pattern acceleration/deceleration B
linear
Time
Acceleration and deceleration
Parameters referred to
3
Base frequency
7
Acceleration time
8
Deceleration time
20
Acceleration/
deceleration reference
frequency
Fig. 6-33:
Characteristic for parameter 29 = "0"
Refer to
Section
6.5.1
6.7.1
6.7.1
6.7.1
I000015C
6 - 77