Change The Control Method (Pr. 80, Pr. 81, Pr. 800) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
6.2.1

Change the control method (Pr. 80, Pr. 81, Pr. 800)

Set when selecting the control method for advanced magnetic flux vector control and general-pur-
pose magnetic flux vector control. The initial value is V/F control.
● Select a control mode using Pr. 800 "Control method selection".
Pr. No. Name
80
Motor capacity
81
Number of motor poles
800
Control method selection
Set a value other than "9999" in Pr. 80 and Pr. 81.
Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
● Motor specifications (motor capacity and number of motor poles) must be set to select advanced
magnetic flux vector control or general-purpose magnetic flux vector control.
● Set the motor capacity (kW) in Pr. 80 "Motor capacity" and set the number of motor poles in Pr. 81
"Number of motor poles".
Selection of control method
Select the inverter control method for V/F control, advanced magnetic flux vector control, and gen-
eral-purpose magnetic flux vector control.
(Pr. 80, Pr. 81 initial value)
Tab. 6-2:
Control method is V/F control regardless of the setting value of Pr. 800 when "9999" is set in
Pr. 80 "Motor capacity" or Pr. 81 "Number of motor poles".
FR-E700 SC EC/ENE
Initial
Setting Range
Value
0.1–15 kW
9999
9999
2/4/6/8/10
9999
9999
20
20
30
Pr. 80, Pr. 81
9999
9999
Selection of control method
Descripton
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Advanced
magnetic flux
vector control
V/F control
General-purpose
magnetic flux
vector control
Pr. 800
20
(Pr. 800 initial value)
30
Control mode
Refer to
Parameters referred to
Section
Advanced magnetic
6.3.2
flux vector control
General-purpose
6.3.3
magnetic flux vector
control
178–184
Input terminal function
6.10.1
selection
450
Second applied motor
6.8.2
44
Second acceleration/
6.7.1
deceleration time
45
Second deceleration
6.7.1
time
46
Second torque boost
6.3.1
47
Second V/F (base
6.5.1
frequency)
48
Second stall prevention
6.3.5
operation current
51
Second electronic
6.8.1
thermal O/L relay
Control Method
Advanced magnetic flux vector con-
trol
General-purpose magnetic flux vector
control
V/F control
6 - 33