Operation Mode (Pr. 79) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Basic settings
5.1.6

Operation mode (Pr. 79)

Select the operation command location and frequency command location.
Pr. No. Name
Operation
79
mode selection
For the terminal used for the X12 signal (PU operation interlock signal) input, assign "12" in
Pr. 178 to Pr. 184 "Input terminal function selection" to assign functions. For Pr. 178 to Pr. 184,
refer to section 6.10.1. When the X12 signal is not assigned, function of the MRS signal switches
from MRS (output stop) to PU operation interlock signal.
NOTE
Setting value "1" to "4" can be changed in the easy operation mode. (Refer to section 4.3.3.)
FR-E700 SC EC/ENE
Initial
Setting
Description
Value
Range
External/PU switch over mode
Press the PU/EXT key to switch between the PU and external
0
operation mode. (Refer to section 4.3.3.)
At power on, the inverter is in the external operation mode.
1
PU operation mode
Fixed to external operation mode
2
Operation can be performed by switching between the external and
Net operation mode.
External/PU combined operation mode 1
Running frequency
Operation panel and PU (FR-
3
PU04/FR-PU07) setting or
external signal input (multi-
speed setting, across terminals 4-
0
5 (valid when AU signal turns
on)).
External/PU combined operation mode 2
Running frequency
4
External signal input (Terminal 2,
4, JOG, multi-speed selection,
etc.)
Switch-over mode
6
Switch among PU operation, external operation, and NET operation
while keeping the same operation status.
External operation mode (PU operation interlock)
X12 signal ON :
Operation mode can be switched to the PU operation mode.
7
(output stop during external operation)
X12 signal OFF :
Operation mode can not be switched to the PU operation mode.
Simple mode parameter list
LED Indication
: OFF
: ON
External operation mode
PU operation mode
External operation mode
NET operation mode
Start signal
External signal input
(terminal STF-, STR)
Start signal
Input using the RUN-key of the
operation panel or FWD/REV of
the PU (FR-PU04/FR-PU07)
PU operation mode
External operation mode
NET operation mode
PU operation mode
External operation mode
5 - 11