Measurements On The Main Circuit; Insulation Resistance Test Using Megger; Pressure Test - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Maintenance and inspection
8.2

Measurements on the main circuit

This section describes the measurement of the main circuit voltages, currents, powers and insulation
resistance.
Please follow as well the instructions for measuring instruments and measuring methods in section
7.7.
8.2.1

Insulation resistance test using megger

For the inverter, conduct the insulation resistance test on the main circuit only as shown below and
do not perform the test on the control circuit. (Use a 500 V DC megger.)
Fig. 8-9:
CAUTION:
E
Before performing the insulation resistance test on the external circuit, disconnect the cables
from all terminals of the inverter so that the test voltage is not applied to the inverter.
NOTE
For the electric continuity test of the control circuit, use a tester (high resistance range) and do not
use the megger or buzzer.
8.2.2

Pressure test

Do not conduct a pressure test. Deterioration may occur.
FR-E700 SC EC/ENE
Power supply
500 V DC megger
Insulation resistance test
Measurements on the main circuit
Earth
I001872E
8 - 11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720s sc ecFr-e720s sc eneFr-e740 sc ecFr-e740 sc ene

Table of Contents