INTRODUCTION

1.1

CC-Link IE TSN communication overview

This product is equipped with a CC-Link IE TSN communication circuit board. Connecting network devices to port 1 or 2 on
the circuit board using an Ethernet cable allows for communication via CC-Link IE TSN.
Personal computer
(FR Configurator2)
NOTE
• Ethernet is a registered trademark of Fuji Xerox Corporation in Japan.
Precautions for CC-Link IE TSN communication
• To maintain the security (confidentiality, integrity, and availability) of the inverter and the system against unauthorized
access, DoS
attacks, computer viruses, and other cyberattacks from external devices via network, take appropriate

measures such as firewalls, virtual private networks (VPNs), and antivirus solutions. We shall have no responsibility or
liability for any problems involving inverter trouble and system trouble by DoS attacks, unauthorized access, computer
viruses, and other cyberattacks.
• Depending on the network environment, the inverter may not operate as intended due to delays or disconnection in
communication. Carefully consider the conditions and safety for the inverter on site.

DoS: A denial-of-service (DoS) attack disrupts services by overloading systems or exploiting vulnerabilities, resulting in a denial-of-service
(DoS) state.
Operation status LEDs
LED
Description
name
RUN
Operation status
Connector for communication
LINK1
(PORT1) status
Connector for communication
LINK2
(PORT2) status
SLMP command request message
ACT
reception status
ERR
Node failure status
L.ERR
Link error

Also lit in no-communication state.

This LED blinks when the MAC address and IP address of the inverter match the MAC address and IP address specified by using engineering
software such as FR Configurator2.

This LED indicates an interruption in communication between the master station and the inverter (due to cables disconnecting/breaking or the
master station powering OFF / resetting).

"
" (duplicate IP address) or "
Programmable controller
RUN
ACT
LINK1
ERR
LINK2
L.ERR
Normal operation (normal
5 V internal voltage)
Link-up
Link-up
-
Node failure

Received data error
" (IP address error) will appear on the operation panel.
CC-Link IE TSN communication overview
Hub
GOT
Inverter
ON
Blinking
-

Data transmission in
progress
Data transmission in
progress
Inverter identification in
progress

-
IP address error
Inverter
OFF
Hardware failure
Link-down
Link-down
Inverter identification
paused
Normal operation
Received data normal

INTRODUCTION
1
3