Mitsubishi Electric FR-E700 Instruction Manual page 281

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0–99:
100–199: Sink logic
Setting
Terminal
Source
Sink
Logic
Logic
0
100
RUN
1
101
SU
3
103
OL
4
104
FU
7
107
RBP
8
108
THP
11
111
RY
12
112
Y12
13
113
Y13
14
114
FDN
15
115
FUP
16
116
RL
20
120
BOF
25
125
FAN
26
126
FIN
46
146
Y46
47
147
PID
64
164
Y64
Tab. 6-31:
Output terminal function assignment (1)
FR-E700 SC EC/ENE
Source logic
Function
Inverter running
Up to frequency
Overload alarm
Output frequency detection
Regenerative brake prealarm
Electronic thermal O/L relay
pre-alarm
Inverter operation ready
Output current detection
Zero current detection
PID lower limit
PID upper limit
PID forward/reverse rotation
output
Brake opening request
Fan fault output
Heatsink overheat prealarm
During deceleration at occurrence
of power failure (retained until
release)
During PID control activated
During retry
Function assignment of external terminals
Operation
Output during operation when
the inverter output frequency
rises to or above Pr. 13 "Starting
frequency".
Output when the output fre-
quency is reached to the set fre-
quency.
Output while stall prevention
function is activated.
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Output when 85% of the regen-
erative brake duty set in Pr. 70 is
reached.
Output when the electronic
thermal relay function cumula-
tive value reaches 85%.
(Electronic thermal relay func-
tion protection (E.THT/E.THM)
activates, when the value
reached 100%.)
Output when the inverter can
be started by switching the
start signal on or while it is run-
ning.
Output when the output cur-
rent is higher than the Pr. 150
setting for longer than the time
set in Pr. 151.
Output when the output power
is lower than the Pr. 152 setting
for longer than the time set in
Pr. 153.
Output when the feedback
value falls below the lower limit
of PID control.
Output when the feedback
value rises above the upper
limit of PID control.
Output when forward rotation
is performed in PID control.
Output to open the brake when
the brake sequence function is
selected.
Output at the time of a fan
fault.
Output when the heatsink tem-
perature reaches about 85% of
the heatsink overheat protec-
tion providing temperature.
Output when the power failure-
time deceleration function is
executed.
Output during PID control.
Output during retry processing. Pr. 65–Pr. 69
Related Parameters Refer to
Page
6-129
Pr. 41
6-131
Pr. 22, Pr. 23, Pr. 66
6-44
Pr. 42, Pr. 43
6-131
Pr. 70
6-103
Pr. 9
6-86
6-129
Pr. 150, Pr. 151
6-133
Pr. 152, Pr. 153
6-133
Pr. 127–Pr. 134
6-293
Pr. 278–Pr. 283,
6-111
Pr. 292
Pr. 244
6-317
7-12
Pr. 261
6-165
Pr. 127–Pr. 134
6-293
6-169
6 - 127