Troubleshooting
7.7.4

Use of CT and transducer

A CT may be used in both the input and output sides of the inverter, but the one used should have the
largest possible VA ability because an error will increase if the frequency gets lower. When using a
transducer, use the effective value calculation type which is immune to harmonics.
7.7.5

Measurement of inverter input power factor

Use the effective power and apparent power to calculate the inverter input power factor. A power-
factor meter cannot indicate an exact value.
Total power factor of the inverter
7.7.6
Measurement of converter output voltage (across terminals P/+ and N/–)
The output voltage of the converter is developed across terminals P/+ and N/– and can be measured
with a moving-coil type meter (tester). Although the voltage varies according to the power supply
voltage, approximately 270 V DC to 300 V DC (540 V DC to 600 V DC for the 400 V class) is output when
no load is connected and voltage decreases during driving load operation.
When energy is regenerated from the motor during deceleration, for example, the converter output
voltage rises to nearly 400 V DC to 450 V DC (800 V DC to 900 V DC for the 400 V class) maximum. When
this value is reached the alarm message E.OV
FR-E700 SC EC/ENE
Effective power
=
----------------------------------------- -
Apparent power
3-phase input power found by 3-wattmeter method
=
---------------------------------------------------------------------------------------------------------------------------------------------------------------------- -
3 V (power supply voltage) I (input current effective value)
is displayed and the inverter output is shut off.