Installation
2.4.2

Inverter placement

Clearances around the inverter
Always observe the specified minimum clearances to ensure good heat dissipation and adequate ac-
cessibility of the frequency inverter for servicing.
Ambient temperature and humidity
5 cm
Temperature: 10 °C to +50 °C
Humidity: 90% RH maximum
Leave enough clearances and take cooling
measures.
Fig. 2-10: Clearances
Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed
above the inverter should be heat resistant.
FR-E700 SC EC/ENE
x = Measurement
position
5 cm
5cm
Clearances (side)
10 cm
1 cm
1 cm
10 cm
When using the inverters at the ambient
temperature of 40 °C or less, the inverters can
be installed without any clearance between
them (0 cm clearance).
When ambient temperature exceeds 40 °C,
clearances between the inverters should be
1 cm or more (5 cm or more for the FR-E740-
120SC or more).
Enclosure design
Clearances (front)
1 cm
5cm for the FR-E740-120SC and
more
I002152E
2 - 11